Shark 100B Dokumentacja Strona 99

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 114
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 98
e
Electro Industries/GaugeTech
Doc #: E145701 D-3
These Objects may be read either by requesting a specific Variation available as listed in this
document, or by requesting Variation 0. READ request for Variation 0 of an Object will be fulfilled
with the Variation listed in this document.
Write ( Function 2 )
Objects supporting the WRITE function are:
Internal Indications ( Object 80 )
Direct Operate ( Function 5 )
Objects supporting the DIRECT OPERATE function are:
Control Relay Output Block ( Object 12 )
Direct Operate - No Acknowledgment ( Function 6 )
Objects supporting the DIRECT OPERATE - NO ACKNOWLEDGMENT function are:
Change to MODBUS RTU Protocol
Response ( Function 129 )
Application responses from Shark meters use the RESPONSE function.
Q
Application Data
Application Data contains information about the Object and Variation, as well as the Qualifier
and Range.
D.4.1:
Object and
Variation
The following Objects and Variations are supported on Shark meters:
Binary Output Status ( Object 10, Variation 2) †
Control Relay Output Block ( Object 12, Variation 1 )
32-Bit Binary Counter Without Flag ( Object 20, Variation 5 ) †
16-Bit Analog Input Without Flag ( Object 30, Variation 4 ) †
Class 0 Data ( Object 60, Variation 1 ) †
Internal Indications ( Object 80, Variation 1 )
† READ requests for Variation 0 will be honored with the above Variations.
D.4.1.1:
Binary
Output
Status
(
Obj.
10,
Var.
2
)
Binary Output Status supports the following functions:
Read ( Function 1 )
A READ request for Variation 0 will be responded to with Variation 2.
Binary Output Status is used to communicate the following data measured by Shark meters: