Shar 100 & 100T
Low Cost, High Performance Multifunction Electricity Meter
e
Electro Industries/GaugeTech
Installation & Operation Manual
Revision 1.12
May 15, 2008
Doc #: E145701 V1.12
1800 Shames Drive
Westbury, New York 11590
Tel: 516-334-0870
X Fax: 516-338-4741
X www.electroind.com
“The Leader in Web Accessed Power Monitoring and Control”
Przeglądanie stron 0
1 2 3 4 5 6 ... 113 114

Podsumowanie treści

Strona 1 - Shar k®100 & 100T

Shar k®100 & 100TLow Cost, High Performance Multifunction Electricity MetereElectro Industries/GaugeTechInstallation & Operation ManualRevisio

Strona 2 - Electro Industries/GaugeTech

eElectro Industries/GaugeTech Doc # E145701 viii

Strona 3 - Doc # E145701

e Electro Industries/GaugeTech Doc # E145701 D-4QEnergy Reset StateChange to MODBUS RTU Protocol StateEnergy Reset State ( Point 0 )Shark meters ac

Strona 4 -

e Electro Industries/GaugeTech Doc #: E145701 D-5• Change to Modbus RTU Protocol ( Point 1 )Shark meters are capable of changing from DNP Protocol

Strona 5

e Electro Industries/GaugeTech Doc # E145701 D-6D.4.1.4: 16-BBit Analog Input Without Flag ( Obj. 30, Var. 4 )Analog Inputs support the

Strona 6

e Electro Industries/GaugeTech Doc # E145701 D-7QPhase-to-Phase Voltage ( Points 4 - 6 )These points are formatted as 2's complement fractions

Strona 7 - Contents

e Electro Industries/GaugeTech Doc # E145701 D-8QPower Factor ( Point 13 )This point is formatted as a 2's complement integer. It represents

Strona 8 - Doc # E145701 vi

e Electro Industries/GaugeTech Doc # E145701 D-9QPhase Angle ( Points 20 - 25 )These points are formatted as 2's complement integers. They r

Strona 9 - Doc # E145701 vii

e Electro Industries/GaugeTech Doc # E145701 D-10D.4.1.5: Class 0 Data ( Obj. 60, Var. 1 )Class 0 Data supports the following functions:Re

Strona 10 - Doc # E145701 viii

E Electro Industries/Gauge Tech Doc# E145721 E-1 Appendix E Using the USB to IrDA Adapter (CAB6490) E.1: Introduction Com 1 o

Strona 11 - Phase C

E Electro Industries/Gauge Tech Doc# E145721 E-2 5. Make sure the first Radio Button and the first Checkbox ar

Strona 12 - Doc # E145701 1-2

E Electro Industries/Gauge Tech Doc# E145721 E-3 8. You do not need to be concerned about the message on the bot

Strona 13 - Doc # E145701 1-3

eElectro Industries/GaugeTech Doc # E145701 1-1Chapter 1Three-PPhase Power MeasurementThis introduction to three-phase power and power

Strona 14 - Doc # E145701 1-4

E Electro Industries/Gauge Tech Doc# E145721 E-4 11. When the driver installation is complete, you will see the s

Strona 15 - Doc # E145701 1-5

E Electro Industries/Gauge Tech Doc# E145721 E-5 This time, click the Radio Button next to Install the soft

Strona 16 - Doc # E145701 1-6

E Electro Industries/Gauge Tech Doc# E145721 E-6 17. When the installation is complete, you w

Strona 17 - Doc # E145701 1-7

E Electro Industries/Gauge Tech Doc# E145721 E-7 Click Finish to close the Found New Hardwar

Strona 18 - Kilowatt-hours

E Electro Industries/Gauge Tech Doc# E145721 E-8 20. Click the Modem tab. The Com Port that the Adapter is using is displayed i

Strona 19 - Doc # E145701 1-9

eElectro Industries/GaugeTech Doc # E145701 1-2Fig 1.2: Phasor diagram showing Three-phase Voltages and CurrentsQThe phasor diagram shows

Strona 20 - Doc # E145701 1-10

1.1.2: Delta ConnectionQDelta connected services may be fed with either three wires or four wires. In a three-phase deltaservice the load windings a

Strona 21 - Doc # E145701 1-11

Fig 1.5: Phasor diagram showing Three-phase, Four-wire Delta Connected System1.1.3: Blondell’s Theorem and Three Phase MeasurementIn 1893 an en

Strona 22

single three-phase reading.Some digital meters calculate the individual phase power values one phase at a time. This means themeter samples the voltag

Strona 23 - Doc # E145701 1-13

1.2: Power, Energy and DemandQIt is quite common to exchange power, energy and demand without differentiating between thethree. Because this prac

Strona 24 - Doc # E145701 1-14

Table 1.2: Power and energy relationship over timeAs in Table 1.2, the accumulated energy for the power load profile of Figure 1.7 is 14.92 kWh. QDem

Strona 25 - (Transducer Only)

QFigure 1.8 shows another example of energy and demand. In this case, each bar represents the energy consumed in a 15-minute interval. The energy use

Strona 26 - Doc #: E145701 2-2

QThe voltage (V) and the total current (I) can be combined to calculate the apparent power or VA.The voltage and the in-phase current (IR) are combine

Strona 27

eElectro Industries/GaugeTechDoc # E145701

Strona 28 - Doc #: E145701 2-4

result, it does not include the impact of harmonic distortion. Displacement power factor is calculatedusing the following equation:Displacement PF = c

Strona 29 - Doc #: E145701 2-5

Figure 1.11: Distorted current waveQThe distortion observed in Figure 1.11 can be modeled as the sum of several sinusoidal waveformsof frequencies tha

Strona 30 - Doc #: E145701 2-6

QInductive and capacitive impedance are present in all power systems. We are accustomed to thinkingabout these impedances as they perform at 60 Hz. Ho

Strona 31 - Introduction

1.5: Power QualityQPower quality can mean several different things. The terms ‘power quality’ and ‘power quality problem’ have been applied to all t

Strona 32 - Doc #: E145701 3-2

eElectro Industries/GaugeTech Doc # E145701 1-14

Strona 33 - Doc #: E145701 3-3

eElectro Industries/GaugeTech Doc #: E145701 2-1Chapter 2Shark® Meter Overview and Specifications 2.1: Hardware OverviewQThe Shark®100

Strona 34 - Figure 3.10: DIN Rail Detail

eElectro Industries/GaugeTech Doc #: E145701 2-22.1.1: Voltage and Current InputsQUniversal Voltage InputsVoltage Inputs allow measure

Strona 35 - Electrical Installation

eElectro Industries/GaugeTech Doc #: E145701 2-32.1.3: V-SSwitch®® TechnologyThe Shark® 100 meter is equipped with EIG’s exclusive V-Swi

Strona 36 - Doc # E145701 4-2

e Electro Industries/GaugeTech Doc #: E145701 2-42.1.5: Utility Peak DemandThe Shark® 100 meter provides user-configured Block (Fixed) Window or

Strona 37 - Doc #: E145701 4-3

eElectro Industries/GaugeTech Doc #: E145701 2-5QIsolation• All Inputs and Outputs are galvanically isolated to 2500 VacQEnvironmental Rat

Strona 38 - Terminations

Shark® 100 & 100T MeterInstallation and Operation ManualVersion 1.12Published by:Electro Industries/GaugeTech1800 Shames DriveWestbury, NY 11590Al

Strona 39 - Doc # E145701 4-5

eElectro Industries/GaugeTech Doc #: E145701 2-62.3: Compliance• IEC 687 (0.2% Accuracy)• ANSI C12.20 (0.2% Accuracy)• ANSI (IEEE) C37.90

Strona 40 - Doc # E145701 4-6

e Electro Industries/GaugeTech Doc # E145701 3-1Chapter 3Mechanical Installation3.1: IntroductionQThe Shark 100 meter can be installed

Strona 41 - Doc #: E145701 4-7

e Electro Industries/GaugeTech Doc #: E145701 3-23.2: ANSI Installation StepsANSI INSTALLATION STEPS:1. Insert 4 threaded rods by hand

Strona 42 - Doc # E145701 4-8

e Electro Industries/GaugeTech Doc #: E145701 3-33.3: DIN Installation Steps DIN INSTALLATION STEPS:1. Slide meter with NEMA 12 Mounti

Strona 43 - Doc #: E145701 4-9

e Electro Industries/GaugeTech Doc # E145701 3-43.4: Shark 100T Transducer InstallationQThe Shark 100T Transducer model is installed u

Strona 44 - Doc # E145701 4-10

eElectro Industries/GaugeTech Doc # E145701 4-1Chapter 4Electrical Installation4.1: Considerations When Installing MetersQInstallati

Strona 45 - Doc # E145701 4-11

eElectro Industries/GaugeTech Doc # E145701 4-24.2: CT Leads Terminated to MeterQThe Shark 100 is designed to have Current Inputs wir

Strona 46

eElectro Industries/GaugeTech Doc #: E145701 4-34.3: CT Leads Pass Through (No Meter Termination)QThe second method allows the CT

Strona 47 - Doc # E145701 4-13

eElectro Industries/GaugeTech Doc #: E145701 4-44.4: Quick Connect Crimp CT Terminations QFor Quick Termination or for Portable Appl

Strona 48

eElectro Industries/GaugeTech Doc # E145701 4-54.5: Voltage and Power Supply ConnectionsQVoltage Inputs are connected to the back of

Strona 49

eElectro Industries/GaugeTech Doc # E145701 iiCustomer Service and SupportCustomer support is available 9:00 am to 4:30 pm, east

Strona 50

eElectro Industries/GaugeTech Doc # E145701 4-61. Service: WYE, 4-Wire with No PTs, 3 CTs4.8: Electrical Connection DiagramsChoose the

Strona 51 - Doc # E145701 5-1

eElectro Industries/GaugeTech Doc #: E145701 4-72. Service: 2.5 Element WYE, 4-Wire with No PTs, 3 CTsSelect: “2.5 EL WYE” (2.5 Element W

Strona 52 - Doc #: E145701 5-2

eElectro Industries/GaugeTech Doc # E145701 4-83. Service: WYE, 4-Wire with 3 PTs, 3 CTsSelect: “3 EL WYE” (3 Element Wye) in Meter Progr

Strona 53 - Doc #: E145701 5-3

eElectro Industries/GaugeTech Doc #: E145701 4-94. Service: 2.5 Element WYE, 4-Wire with 2 PTs, 3 CTsSelect: “2.5 EL WYE” (2.5 Element Wy

Strona 54 - Doc #: E145701 5-4

eElectro Industries/GaugeTech Doc # E145701 4-105. Service: Delta, 3-Wire with No PTs, 2 CTs Select: “2 Ct dEL” (2 CT Delta) in Meter Pro

Strona 55 - Doc #: E145701 5-5

eElectro Industries/GaugeTech Doc # E145701 4-116. Service: Delta, 3-Wire with 2 PTs, 2 CTs Select: “2 Ct dEL” (2 CT Delta) in Meter Prog

Strona 56 - Doc #: E145701 5-6

eElectro Industries/GaugeTech Doc #: E145701 4-127. Service: Delta, 3-Wire with 2 PTs, 3 CTs Select: “2 Ct dEL” (2 CT Delta) in Meter Pro

Strona 57 - Doc #: E145701 5-7

eElectro Industries/GaugeTech Doc # E145701 4-138. Service: Current Only Measurement (Three Phase)* Even if the meter is used for only a

Strona 58 - Doc #: E145701 5-8

eElectro Industries/GaugeTech Doc #: E145701 4-149. Service: Current Only Measurement (Dual Phase)* Even if the meter is used for only a

Strona 59 - Doc #: E145701 5-9

eElectro Industries/GaugeTech Doc #: E145701 4-15* Even if the meter is used for only amp readings, the unit requires a Voltage reference

Strona 60 - Doc #: E145701 5-10

eElectro Industries/GaugeTech Doc # E145701 iiiAbout Electro Industries/GaugeTec

Strona 61 - Doc #: E145701 5-11

eElectro Industries/GaugeTech Doc #: E145701 4-16

Strona 62 - Doc #: E145701 5-12

e Electro Industries/GaugeTech Doc # E145701 5-1Chapter 5Communication Installation5.1: Shark 100 CommunicationQThe Shark 100 meter provides

Strona 63 - Doc # E145701 6-1

eElectro Industries/GaugeTech Doc #: E145701 5-25.1.2: RS-4485 Communication Com 2 (485 Option)QThe Shark 100 meter’s RS-485 port uses standar

Strona 64 - Doc #: E145701 6-2

eElectro Industries/GaugeTech Doc #: E145701 5-35.1.3: RS-4485 / KYZ Output Com 2 (485P Option)QThe 485P Option provides a combination RS-48

Strona 65 - Doc #: E145701 6-3

eElectro Industries/GaugeTech Doc #: E145701 5-4Figure 5.5 shows the detail of a 2-wire RS485 connection.Figure 5.5: 2-wire RS485 ConnectionNOTES: F

Strona 66 - Doc # E145701 6-4

eElectro Industries/GaugeTech Doc #: E145701 5-5Figure 5.7: Incorrect “T” and “Star” Topologies

Strona 67 - Figure 7.2: Wh Reading

eElectro Industries/GaugeTech Doc #: E145701 5-655..11..33..11:: UUssiinngg tthhee UUnniiccoomm 22550000The Unicom 2500 provides RS485/RS232 con

Strona 68 - Doc #: E145701 7-2

eElectro Industries/GaugeTech Doc #: E145701 5-75.2: Shark 100T Communication and Programming OverviewQThe Shark 100T Transducer model does n

Strona 69 - Doc #: E145701 7-3

eElectro Industries/GaugeTech Doc #: E145701 5-8The Device Status screen appears, confirming a connection. Click OK. The main screen of Communicat

Strona 70 - Doc # E145701 7-4

eElectro Industries/GaugeTech Doc #: E145701 5-95.2.2: Shark Profile SettingsQScaling (CT, PT Ratios and System Wiring)CT Numerator (Primary):CT

Strona 71 - Doc #: E145701 7-5

eElectro Industries/GaugeTech Doc # E145701 iv

Strona 72 - Doc # E145701 7-6

eElectro Industries/GaugeTech Doc #: E145701 5-10QEnergy and DisplayPower and Energy FormatPower ScaleEnergy DigitsEnergy Decimal PlacesEnergy Scale

Strona 73 - Doc # E145701 7-7

eElectro Industries/GaugeTech Doc #: E145701 5-11QSettingsPassword (Meter is shipped with Password Disabled andthere is NO DEFAULT PASSWORD)Enable

Strona 74 - 2 CT Delta

eElectro Industries/GaugeTech Doc #: E145701 5-12

Strona 75

eElectro Industries/GaugeTech Doc # E145701 6-1Chapter 6Using the Meter6.1: IntroductionQThe Shark 100 meter can be configured and a v

Strona 76 - Doc # E145701 7-10

eElectro Industries/GaugeTech Doc #: E145701 6-2QEnter Button: Press and release to enter one of four Display ModesOperating Mode (Defaul

Strona 77 - Doc # E145701 A-1

eElectro Industries/GaugeTech Doc #: E145701 6-36.3: Watt-HHour Accuracy Testing(Verification)QTo be certified for revenue metering, po

Strona 78 - Doc #: E145701 A-2

eElectro Industries/GaugeTech Doc # E145701 6-46.4: Upgrade the Meter Using V-SSwitches®®QThe Shark 100 is equipped with V-Switch® Te

Strona 79 - Doc #: E145701 A-3

eElectro Industries/GaugeTech Doc # E145701 7-1Chapter 7Configuring the Shark Using the Front Panel7.1: OverviewQThe Shark 100 front panel

Strona 80 - Doc # E145701 A-4

eElectro Industries/GaugeTech Doc #: E145701 7-27.3: Configuration7.3.1: Main Menu QPush MENU from any of the Auto-Scrolling Readings. The MAI

Strona 81 - Doc # E145701 A-5

eElectro Industries/GaugeTech Doc #: E145701 7-37.3.2.1: Enter Password (ONLY IF ENABLED IN SOFTWARE)QTo enter a Password: If PASSWORD is Enabl

Strona 82 - Doc # E145701 A-6

Table of ContentsEIG Warranty iiChapter 1: Three-Phase Power Measurement1.1: Three-Phase System Configurations . . . . . . . . . . .

Strona 83 - Doc # E145701 B-1

eElectro Industries/GaugeTech Doc # E145701 7-47.3.3: Configuration ModeQThe next Mode on the Main Menu is Configuration Mode. See Appendix A f

Strona 84 - Doc # E145701 B-2

eElectro Industries/GaugeTech Doc #: E145701 7-57.3.3.2: Program Configuration Mode ScreensQTo program the screens in Configuration Mode, othe

Strona 85 - Fixed Data Section

eElectro Industries/GaugeTech Doc # E145701 7-67.3.3.3: Configure CT SettingPush the DOWN Button to scroll all the parameters in Configuration M

Strona 86

eElectro Industries/GaugeTech Doc # E145701 7-77.3.3.4: Configure PT SettingPush the DOWN Button to scroll all the parameters in Configuration M

Strona 87

eElectro Industries/GaugeTech Doc # E145701 7-87.3.3.5: Configure Connection (Cnct) SettingPush the DOWN Button to scroll all the parameters in

Strona 88 - Commands Section

eElectro Industries/GaugeTech Doc # E145701 7-97.3.3.6: Configure Communication Port SettingPush the DOWN Button to scroll all the parameters i

Strona 89

eElectro Industries/GaugeTech Doc # E145701 7-107.3.4: Operating ModeQOperating Mode is the Shark 100 meter’s Default Mode. After Start Up, the

Strona 90

eElectro Industries/GaugeTech Doc # E145701 A-1Appendix AShark Navigation MapsA.1: IntroductionQThe Shark 100 meter can be configured

Strona 91

eElectro Industries/GaugeTech Doc #: E145701 A-2

Strona 92 - End of Ma

eElectro Industries/GaugeTech Doc #: E145701 A-3

Strona 93 - Doc # E145701 C-1

5.2.1: Factory Initial Default Settings . . . . . . . . . . . . . . . . . . . . . . 5-75.2.2: Shark® Meter Profile Settings .

Strona 94 - Doc #: E145701 C-2

eElectro Industries/GaugeTech Doc # E145701 A-4

Strona 95

eElectro Industries/GaugeTech Doc # E145701 A-5

Strona 96

eElectro Industries/GaugeTech Doc # E145701 A-6

Strona 97 - Doc # E145701 D-1

e Electro Industries/GaugeTech Doc # E145701 B-1Appendix BModbus Mapping for SharkB.1: IntroductionQThe Modbus Map for the Shark 100

Strona 98 - Doc #: E145701 D-2

e Electro Industries/GaugeTech Doc # E145701 B-2B.4: Floating Point ValuesQFloating Point Values are represented in the following forma

Strona 99 - Doc #: E145701 D-3

Description1Format Range6Units or Resolution Comments# Regread-only0000 - 0007 1 - 8 Meter Name ASCII 16 char none 80008 - 000F 9 - 16 Meter Serial Nu

Strona 100 - Doc # E145701 D-4

Description1Format Range6Units or Resolution Comments# RegModbus AddressHex Decimal044B - 044C 1100 - 1101 W-hours, Received SINT32 0 to 99999999 or

Strona 101 - Doc #: E145701 D-5

Description1Format Range6Units or Resolution Comments# RegModbus AddressHex Decimal0BD5 - 0BD6 3030 - 3031 Negative Power Factor, 3-Ph, Minimum Avg De

Strona 102 - 3 Phase CN Voltage

Description1Format Range6Units or Resolution Comments# RegModbus AddressHex Decimal0FAF - 0FAF 4016 - 4016 Phase A Voltage 2nd harmonic magnitude UINT

Strona 103 - Doc # E145701 D-7

Description1Format Range6Units or Resolution Comments# RegModbus AddressHex Decimal55F2 - 55F2 22003 - 22003Programmable Settings Checksum3UINT16read/

Strona 104 - Doc # E145701 D-8

Appendix C: DNP Mapping for Shark®100 MeterC.1: Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Strona 105 - Doc # E145701 D-9

Description1Format Range6Units or Resolution Comments# RegModbus AddressHex Decimal7536 - 7536 30007 - 30007 Operating Mode Screen Enables UINT16 bit-

Strona 106 - Doc # E145701 D-10

Description1Format Range6Units or Resolution Comments# RegModbus AddressHex Decimal7569 - 756D 30058 - 30062 Limit #7 SINT16 5756E - 7572 30063 - 3006

Strona 107 - Appendix E

Description1Format Range6Units or Resolution Comments# RegModbus AddressHex DecimalNotes123456789101112currentFS = CT numerator * CT multipliervoltage

Strona 108 - Electro Industries/Gauge Tech

e Electro Industries/GaugeTech Doc # E145701 C-1Appendix CDNP Mapping for SharkC.1: IntroductionQThe DNP Map for the Shark 100 Meter

Strona 109

e Electro Industries/GaugeTech Doc #: E145701 C-2

Strona 110

Object Point Var Description Format RangeMultiplier Units CommentsRead via Class 0 only10 0 2 Reset Energy Counters BYTE Always 1N/A none10 1 2 Change

Strona 111

Object Point Var Description Format RangeMultiplier Units Comments30 10 5 Watts, 3-Ph total SINT16 -32768 to +32767 (4500 / 32768)W30 11 5 VARs, 3-Ph

Strona 112

e Electro Industries/GaugeTech Doc # E145701 D-1Appendix DDNP 3.0 Protocol Assignments for SharkD.1: DNP ImplementationQPHYSICAL LAYERThe

Strona 113

e Electro Industries/GaugeTech Doc #: E145701 D-2place. Unconfirmed communication is always possible and does not require a RESET.User Data ( Funct

Strona 114

e Electro Industries/GaugeTech Doc #: E145701 D-3These Objects may be read either by requesting a specific Variation available as listed in this do